JYH-6~10k

JYH-6~10k

Technical Parameters

MODEL Combo 6K(L) Combo 10K(L)
PHASE 1 phase in / 1 phase out
CAPACITY 6000 VA / 4800 W 10000 VA / 8000 W
INPUT
Nominal Voltage  208/220/230/240VAC
Voltage Range Low Line Loss  110 VAC ± 3% at 50% Load
176 VAC ± 3% at 100% Load
Low Line Comeback  120 VAC ± 3% at 50% Load
186 VAC ± 3% at 100% Load
High Line Loss  300 VAC ± 3%
High Line Comeback  290 VAC ± 3%
Frequency Range
46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Power Factor ≧ 0.99  @ 100% load
OUTPUT
Nominal Voltage  208/220/230/240VAC
AC Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦ 3 % THD (Linear Load)
≦ 6 % THD (Non-linear Load)
Transfer Time Bypass to Inverter (Line mode) Zero
Inverter to Bypass (Line mode) Zero
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
Line Mode 89% 90%
Battery Mode 88% 89%
BATTERY
Standard Model Battery Type 12 V / 7 AH 12 V / 9 AH
Numbers 16 16
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current Default:1.0 A ±  10%, Max.:2.0A ±  10% Default:1.0 A ±  10%, Max.:2.0A ±  10%
Float Charging Voltage 218.4 VDC ±  1%
Long-run Model Battery Type Depending on applications
Numbers 16-20** (adjustable)
Charging Current Default:4.0 A ±  10%,  Max.:6.0A ±  10% Default:4.0 A ±  10%,  Max.:6.0A ±  10%
Float Charging Voltage 273 VDC ±  1% (based on 20 pcs batteries)
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension, D X W X H (mm) 369 x 190 x 688 442 x 190 x 688
Net Weight (kgs) 60 75
Long-run Model Dimension, D X W X H (mm) 369 x 190 x 318 442 x 190 x 318
Net Weight (kgs) 21 23
ENVIRONMENT
Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 55dBA @ 1 Meter Less than 58dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser

*Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.

*If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice